Refrigerant Charge Calculator — Superheat and Subcooling

Determine refrigerant charge status by calculating actual superheat and subcooling values, then comparing them to target ranges. Supports both TXV/EEV and fixed-orifice metering device systems.

System Configuration

Superheat Method (Fixed Orifice / Piston)

Target Superheat Inputs (Fixed Orifice Systems)

Formulas

Actual Superheat (Fixed Orifice Systems):

Superheat (°F) = Tsuction line − Tsat @ suction pressure

Where Tsat @ suction pressure is the saturation (boiling) temperature of the refrigerant at the measured suction line gauge pressure, obtained from refrigerant pressure-temperature tables.

Target Superheat (Fixed Orifice Systems):

Determined by bilinear interpolation of the AHRI/manufacturer superheat charging chart using: outdoor ambient dry-bulb temperature and indoor return air wet-bulb temperature. The chart encodes the relationship between heat load, airflow, and required evaporator performance.

Actual Subcooling (TXV / EEV Systems):

Subcooling (°F) = Tsat @ liquid line pressure − Tliquid line

Where Tsat @ liquid line pressure is the condensing saturation temperature at the measured liquid line gauge pressure. Subcooling confirms all refrigerant has condensed to liquid before the metering device.

Saturation Temperature Interpolation:

Tsat(P) = T0 + (P − P0) × (T1 − T0) / (P1 − P0)

Linear interpolation between adjacent data points in the refrigerant P-T table.

Assumptions & References