Humidity & Ventilation Load Calculator

Account for West Virginia's variable humidity levels in HVAC system sizing. Calculates latent and sensible ventilation loads per ASHRAE 62.1 and Manual J principles.

Space & Occupancy

WV Climate Conditions

Indoor Design Conditions

Ventilation Parameters

Formulas Used

Humidity Ratio (W):
W = 0.62198 × (φ × Pws) / (Psite − φ × Pws)  [lb water / lb dry air]
where Pws = saturation pressure (Magnus formula), φ = relative humidity fraction, Psite = barometric pressure corrected for WV elevation.

Enthalpy of Moist Air:
h = 0.240·T + W·(1061 + 0.444·T)  [BTU/lb dry air]

Sensible Ventilation Load:
Qs = 1.1 × CFM × ΔT  [BTU/hr]
(1.1 = 60 min/hr × 0.075 lb/ft³ × 0.240 BTU/lb·°F)

Latent Ventilation Load:
Ql = 0.68 × CFM × ΔWgrains  [BTU/hr]
(0.68 = 60 × 0.075 × 1076 / 7000; 1076 BTU/lb = latent heat of vaporization)

ASHRAE 62.1 Ventilation Rate:
CFM = (Occupants × Rp) + (Floor Area × Ra)

ERV/HRV Recovery:
Tsupply = Tout + εs·(Tin − Tout)
Wsupply = Wout + εl·(Win − Wout)

Altitude Correction (WV elevations 565–4,863 ft):
Psite = 14.696 × (1 − 6.8754×10⁻⁶ × elevation)5.2559 psia