Austin Climate Load Calculator

Estimates residential heating and cooling loads for Austin, TX using the Manual J simplified method with Austin-specific climate design conditions (ASHRAE 99%/1% design temperatures).

Building Envelope

Construction & Infiltration

Formulas Used

Conduction: Q = U × A × ΔT  (BTU/hr)

Solar gain: Qsolar = SHGC × Awin × SHGF × IAC

Infiltration (sensible): Q = 1.1 × CFM × ΔT

Infiltration (latent): Q = 0.68 × CFM × Δgrains

CFM: ACH × Volume / 60  |  ACH = factor × (ΔT/10)0.4

Slab edge (heating): Q = F2 × Perimeter × ΔT  (F2 = 0.73 BTU/hr·ft·°F)

Duct losses: 15% cooling / 20% heating (attic ducts, Austin typical)

Cooling tons: Total BTU/hr ÷ 12,000

Assumptions & References

  • Austin design conditions (ASHRAE 2021): Cooling 101°F DB / 76°F WB (99th percentile); Heating 28°F DB (99th percentile)
  • Slab edge factor F2 = 0.73 BTU/hr·ft·°F (ASHRAE, uninsulated slab, Austin soil)
  • References: ASHRAE Handbook of Fundamentals 2021; ACCA Manual J 8th Ed.; ACCA Manual S; Austin Energy Green Building Guidelines; Texas IECC 2021